Nortel DMS-100 Series Replacement Procedures page 54

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-22 XPM card replacement procedures (continued)
NT6X85
in an SMS-R
(continued)
21
Switch settings for NT6X85AB and NT6X85AC with 8 dip switches
Distance
0 m to 91 m (0 ft to 300 ft)
92 m to 137 m (301 ft to 452 ft)
138 m to 200 m (453 ft to 655 ft)
Switch settings for NT6X85AC with 3 dip switches for 24 AWG DS-1 cable
Card release and length of cables
NT6X85AC, release 4 version 1
0 m to 27 m (0 ft to 86 ft)
27 m to 55 m (86 ft to 180 ft)
55 m to 82 m (180 ft to 269 ft)
82 m to 110 m (269 ft to 361 ft)
110 m to 116 m (361 ft to 380 ft)
Switch settings for NT6X85AC with 3 dip switches for 22 AWG DS-1 cable
(Sheet 1 of 2)
Card release and length of cables
NT6X85AC, release 4 version 1
0 m to 41 m (0 ft to 133 ft)
41 m to 81 m (133 ft to 266 ft)
81 m to 122 m (266 ft to 399 ft)
297-8021-547 Standard 14.02 May 2001
You have successfully completed this procedure. Return to the maintenance
procedure that directed you to this card replacement procedure and continue
as directed.
The following tables describe the dip switch settings for the NT6X85AB and
NT6X85AC cards.
Leave the switch contacts ON
and leave all others OFF
SW2 SSW4
SW3 SW6 SW8
SW1 SW5 SW7
Leave the switch contacts ON
and leave all others OFF
SW1
SW2 SW3
SW2
SW3
None, all contacts are to be open
Leave the switch contacts ON
and leave all others OFF
SW1
SW2 SW3
SW2