Nortel DMS-100 Series Replacement Procedures page 115

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

At the MAP terminal
8
Busy the inactive PM unit by typing
>bsy unit rcc2_unit_no
and pressing the Enter key.
where
rcc2_unit_no
is the number of the inactive RCC2 unit (0 or 1)
At the RCE frame
9
Put on a wrist strap.
10
Remove the NT6X92 card as shown in the following figures.
a
Locate the card to be removed on the appropriate shelf.
DMS-100 Family NA100 Card Replacement Procedures Volume 6 of 7 LET0015 and up
XPM card replacement procedures (continued)
in an RSC-S (DS-1) Model A RCC2
WARNING
Static electricity damage
Before removing any cards, put on a wrist strap and connect
it to the wrist strap grounding point on the left side of the
frame supervisory panel (FSP) of the RCC2. This protects
the equipment against damage caused by static electricity.
DANGER
Equipment damage
Take these precautions when removing or inserting a card:
1. Do not apply direct pressure to the components.2. Do not
force the card into its slot.
1-83
NT6X92
(continued)