Nortel DMS-100 Series Replacement Procedures page 345

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

in an RSC-S (PCM-30) Model A RCO2
and press the Enter key.
If the LOADFW
passes
fails
21
To upgrade the firmware on the inactive unit type:
>LOADFW INACTIVE UPGRADE
and press the Enter key.
If the LOADFW UPGRADE
passes
fails
22
To return the inactive RCO2 unit to service, type:
>RTS UNIT unit_no
and press the Enter key.
where
unit_no
is the number of the inactive RCO2 unit
If RTS
passes
fails
At the RCE frame
23
Remove the sign from the active RCO2 unit.
24
Send the defective cards for repair according to local procedure.
25
Note the following in the office records:
date the card is replaced
serial number of the card
problems that prompted replacement of the card.
Go to step 28.
Return to the Clearing an Alarm Procedure or other procedure that directed
26
you to this procedure. If necessary, go to the point where the system
produced the defective card list. Identify the next defective card on the list,
and go to the appropriate procedure for that card in this manual.
27
For additional help, contact the next level of support.
DMS-100 Family NA100 Card Replacement Procedures Volume 6 of 7 LET0015 and up
XPM card replacement procedures (continued)
Do
step 21
step 27
Do
step 22
step 27
Do
step 23
step 27
1-313
NTAX74
(continued)