Nortel DMS-100 Series Replacement Procedures page 400

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-368 XPM card replacement procedures (continued)
NTAX78
in an SMA-MVI-20
At the equipment frame
20
21
22
23
24
297-8021-547 Standard 14.02 May 2001
(end)
where
unit_no
is the number of the SMA unit loaded in step 18
If RTS
passed
failed
Remove the sign from the active SMA unit.
Send any faulty cards for repair according to local procedure.
Note the following in the office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card
Go to step 24.
For further assistance, contact the personnel responsible for the next level of
support.
You have successfully completed this procedure. Return to the maintenance
procedure that directed you to this card replacement procedure and continue
as directed.
Do
step 20
step 23