Nortel DMS-100 Series Replacement Procedures page 444

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-412 XPM card replacement procedures (continued)
NTBX01
in an
At the MAP terminal
8
At the RCE frame
9
10
297-8021-547 Standard 14.02 May 2001
Busy the inactive PM unit by typing
>bsy unit rco2_unit_no
and pressing the Enter key.
where
rco2_unit_no
is the number of the inactive RCO2 unit (0 or 1)
WARNING
Static electricity damage
Before removing any cards, put on a wrist strap and connect
it to the wrist strap grounding point on the left side of the
modular supervisory panel of the RCO2. This protects the
equipment against damage caused by static electricity.
DANGER
Equipment damage
Take these precautions when removing or inserting a card:
1. Do not apply direct pressure to the components.2. Do not
force the card into its slot.
Put on a wrist strap.
Remove the NTBX01 card as shown in the following figures.
a
Locate the card to be removed on the appropriate shelf.
RSC-S (PCM-30) Model B RCO2