Nortel DMS-100 Series Replacement Procedures page 424

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-392 XPM card replacement procedures (continued)
NTBX01
in an RSC-S (DS-1) Model B RCC2
Replacing an NTBX01 card in RSC-S RCC2
At your Current Location
1
2
At the MAP terminal
3
297-8021-547 Standard 14.02 May 2001
Proceed only if you have been directed to this card replacement procedure
from a step in a maintenance procedure, are using the procedure for verifying
or accepting cards, or have been directed to this procedure by your
maintenance support group.
CAUTION
Loss of service
When replacing a card in the RCC2, ensure that the unit in
which you are replacing the card is inactive and that the mate
unit is active.
Obtain an NTBX01 replacement card. Ensure the replacement card has the
same product equipment code (PEC), including suffix, as the card that is to
be removed.
Ensure the PM level of the MAP display is currently displayed and the RCC2
is posted by typing
>MAPCI;MTC;PM;POST RCC2 rcc2_unit_no
and pressing the Enter key.
where
rcc2_unit_no
is the number of the RCC2 with the faulty card
Example of a MAP display:
(continued)