Nortel DMS-100 Series Replacement Procedures page 399

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

At the equipment frame
15
Perform the common replacing a card procedure in this document.
16
Use the following information to determine the next step.
If you were directed here from
alarm clearing procedures
other
17
Reset the unit by typing
PMRESET UNIT unit_no
and pressing the Enter key.
where
unit_no
is the number of the inactive SMA unit (0 or 1)
At the MAP terminal
18
Load the inactive SMA unit by typing
>LOADPM UNIT unit_no
and pressing the Enter key.
where
unit_no
is the number of the busied SMA unit
If load
passed
failed
19
Return the inactive SMA unit to service by typing
>RTS UNIT unit_no
and pressing the Enter key.
DMS-100 Family NA100 Card Replacement Procedures Volume 6 of 7 LET0015 and up
XPM card replacement procedures (continued)
in an SMA-MVI-20
WARNING
Static electricity damage
Before removing any cards, put on a wrist strap and connect
it to the wrist strap grounding point on the frame supervisory
panel (FSP). This protects the equipment against damage
caused by static electricity.
Do
step 20
step 17
Do
step 19
step 23
1-367
NTAX78
(continued)