Nortel DMS-100 Series Replacement Procedures page 101

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

RCO2
Unit0:
Unit1:
Bsy INACTIVE
RCO2 0 Unit 0
If the BSY command
passes
fails
At the shelf
11
Locate the circuit card to replace.
Note: The NT6X92 circuit cards, are in slots 6 and 7 of unit 0, and slots
21 and 22 of unit 1.
12
To replace the card, use the common replacing a card procedure in this
document. Complete the procedure and return to this point.
Note: If the card you replace has switches, make sure the switches on the
replacement circuit card have the same settings.
13
The next action depends on the reason you performed this procedure.
If a maintenance procedure
directs you to this procedure
does not direct you to this proce-
dure
14
Remove the sign from the active unit. Return to the maintenance procedure
that sent you to this procedure. Continue as directed.
DMS-100 Family NA100 Card Replacement Procedures Volume 6 of 7 LET0015 and up
XPM card replacement procedures (continued)
0 ISTb
Links_OOS: CSide
Inact ManB
Act
ISTb
Bsy Passed
WARNING
Static electricity damage
Wear a wrist strap that connects to the wrist-strap grounding
point of the modular supervisory panel (MSP) to handle
circuit cards. The wrist strap protects the cards against static
electricity damage.
in an RSC-M
0 , PSide
Do
step 11
step 19
Do
step 14
step 15
1-69
NT6X92
(continued)