Nortel DMS-100 Series Replacement Procedures page 737

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

and pressing the Enter key.
If SWRG
passed
failed
16
Send any faulty cards for repair according to local procedure.
17
Record the date the card was replaced, the serial number of the card, and the
symptoms that prompted replacement of the card. Go to step 20.
18
Return to the procedure that directed you to this procedure. At the point
where a faulty card list was produced, identify the next faulty card on the list
and go to the appropriate card replacement procedure for that card in this
manual.
19
Obtain further assistance in replacing this card by contacting operating
company maintenance personnel.
20
You have successfully completed this procedure. Return to the maintenance
procedure that directed you to this card replacement procedure and continue
as directed.
DMS-100 Family NA100 Card Replacement Procedures Volume 6 of 7 LET0015 and up
XPM card replacement procedures (continued)
Do
step 16
step 19
NTBX72
in an RSC LCME
1-705
(end)