Srx5800 Services Gateway Grounding-Cable Lug Specification - Juniper SRX5800 Hardware Manual

Services gateway
Hide thumbs Also See for SRX5800:
Table of Contents

Advertisement

WARNING:
to ensure proper operation, you must properly ground the services gateway chassis
before connecting power. See
for instructions.

SRX5800 Services Gateway Grounding-Cable Lug Specification

The accessory box shipped with the services gateway includes the cable lug that attaches to the grounding
cable (see
Figure 24 on page
grounding points.
Figure 24: Grounding Cable Lug
End view
0.28
diameter
0.55
each hole
0.08
0.25
0.625
CAUTION:
attach a cable lug to the grounding and power cables that you supply. A cable with an
incorrectly attached lug can damage the services gateway.
NOTE:
The same cable lug is used for the DC power cables.
To meet safety and electromagnetic interference (EMI) requirements and
"Grounding the SRX5800 Services Gateway" on page 239
68) and two UNC 1/4–20 screws used to secure the grounding cable to the
2.25
Crimp area
All measurements in inches
0.37
Before services gateway installation begins, a licensed electrician must
6 AWG conductor
68