Dc Power Cable Lug Specifications For The Srx5800 Services Gateway - Juniper SRX5800 Hardware Manual

Services gateway
Hide thumbs Also See for SRX5800:
Table of Contents

Advertisement

CAUTION:
The power source cables might be labeled (+) and (–) to indicate their polarity. There
is no standard color coding for DC power cables. The color coding used by the external
DC power source at your site determines the color coding for the leads on the power
cables that attach to the terminal studs on each power supply.

DC Power Cable Lug Specifications for the SRX5800 Services Gateway

The accessory box shipped with the services gateway includes the cable lugs that attach to the terminal
studs of each power supply (see
Figure 21: DC Power Cable Lug
End view
0.28
diameter
0.55
each hole
0.08
0.25
0.625
CAUTION:
attach a cable lug to the grounding and power cables that you supply. A cable with an
incorrectly attached lug can damage the services gateway.
WARNING:
access location. It has a separate protective earthing terminal [Metric -M6 and English
- ¼-20 screw) ground lugs] provided on the chassis. This separate protective earth
terminal must be permanently connected to earth.
You must ensure that power connections maintain the proper polarity.
Figure 21 on page
64).
2.25
Crimp area
All measurements in inches
0.37
Before services gateway installation begins, a licensed electrician must
The services gateway is a pluggable type A equipment installed in restricted
6 AWG conductor
64