Juniper SRX5800 Hardware Manual page 452

Services gateway
Hide thumbs Also See for SRX5800:
Table of Contents

Advertisement

PEM 1:
State:
Online
AC input:
OK (1 feed expected, 2 feed connected)
Capacity:
1700 W (maximum 4100 W)
DC output: 741 W (zone 1, 13 A at 57 V, 43% of capacity)
PEM 2:
State:
Empty
Input:
Absent
PEM 3:
State:
Empty
Input:
Absent
System:
Zone 0:
Capacity:
Allocated power:
Actual usage:
Zone 1:
Capacity:
Allocated power:
Actual usage:
Total system capacity: 5800 W (maximum 8200 W)
Total remaining power: 3455 W
The output of the show chassis power command shows that; on PEM 0 two AC input feeds are expected
and two AC input feeds are connected and on PEM 1 one AC input feed is expected and two AC input
feeds are connected.
2. Issue the show chassis alarms command to see if there are any active alarms and the position of the
PEM DIP switch.
> show chassis alarms
1 alarms currently active
Alarm time
2017-01-23 05:05:17 PST
The output of the show chassis alarms command shows one active alarm on PEM 1 and the position
of the DIP switch as 0.
In this example output, there is an alarm on PEM 1 because there is a need of only one AC feed but
the PEM 1 is connected with two AC feeds and the DIP switch position is 0.
4100 W (maximum 4100 W)
1255 W (2845 W remaining)
798 W
1700 W (maximum 4100 W)
1090 W (610 W remaining)
741 W
Class
Description
Minor
PEM 1 Dipswitch 0 Feed Connection 2