Table 17: AC Power Supply Electrical Specifications (continued)
Item
AC input current rating
AC input voltage
AC input line frequency
Efficiency
Table 18: AC Power System Specifications
Item
Redundancy
Output power (maximum) per
supply
Output power (maximum) per
system

AC Power Cord Specifications for the SRX5800 Services Gateway

Each AC power supply has a single AC appliance inlet located in the chassis directly above the power
supply that requires a dedicated AC power feed. Most sites distribute power through a main conduit that
leads to frame-mounted power distribution panels, one of which can be located at the top of the rack that
houses the services gateway. An AC power cord connects each power supply to the power distribution
panel.
The services gateway is not shipped with AC power cords. You must order power cords separately using
the model number shown in
cord inserts into the AC appliance inlet coupler, type C20 (right angle) as described by International
Specification
Standard-Capacity
11 A @ 240 VAC maximum
Operating range: 200 to 240 VAC
50 to 60 Hz
~88%
NOTE:
This value is at full load and nominal voltage.
High-Capacity
Two AC inputs for each
Normal-Capacity
power supply
3+1
2+2
1700 W
4100 W
5100 W
8200 W
Table 19 on page
56. The C19 appliance coupler at the female end of the
High-Capacity
13 A @ 240 VAC maximum per AC input (26 A
per power supply when two AC inputs are used)
One AC input for each
power supply
2+2
1700 W
3400 W