Srx5800 Services Gateway Grounding Cable Specifications - Juniper SRX5800 Hardware Manual

Services gateway
Hide thumbs Also See for SRX5800:
Table of Contents

Advertisement

cable lug that attaches to the grounding cable and two UNC 1/4–20 screws used to secure the grounding
cable to the right-side grounding point on the services gateway.
Figure 23: SRX5800 Services Gateway Chassis Grounding Points
M6 (Metric)
Grounding Point
To ground the services gateway, you must connect a grounding cable to earth ground and then attach it
to the chassis grounding point using the two screws provided.
NOTE:
Additional grounding is provided to an AC-powered services gateway when you plug its
power supplies into grounded AC power receptacles.

SRX5800 Services Gateway Grounding Cable Specifications

The grounding cable that you provide must meet the specifications in
Table 26: Grounding Cable Specifications
Cable Type
Grounding
1/4-20 Grounding Point
Quantity and Specification
2
One 6-AWG (13.3 mm
), minimum 60°C wire, or as required by the local code
Table 26 on page
67.
67