SRX5800 Services Gateway Grounding-Cable Lug Specification

Related
Documentation
Copyright © 2015, Juniper Networks, Inc.
services gateway chassis before connecting power. See
SRX5800 Services Gateway" on page 220
Grounding the SRX5800 Services Gateway on page 220
SRX5800 Services Gateway Chassis Grounding Point Specifications on page 127
SRX5800 Services Gateway Grounding-Cable Lug Specification on page 129
The accessory box shipped with the services gateway includes the cable lug that attaches
to the grounding cable (see
secure the grounding cable to the grounding points.

Figure 69: Grounding Cable Lug

End view
0.28
diameter
0.55
each hole
0.08
0.25
0.625
CAUTION:
Before services gateway installation begins, a licensed electrician
must attach a cable lug to the grounding and power cables that you supply.
A cable with an incorrectly attached lug can damage the services gateway.
NOTE:
The same cable lug is used for the DC power cables.
Grounding the SRX5800 Services Gateway on page 220
SRX5800 Services Gateway Chassis Grounding Point Specifications on page 127
SRX5800 Services Gateway Grounding Cable Specifications on page 128
Figure 69 on page
129) and two UNC 1/4–20 screws used to
2.25
Crimp area
All measurements in inches
0.37
Chapter 10: Grounding Specifications
"Grounding the
for instructions.
6 AWG conductor
129