Application Selection; Application Selection; Setting 1: Water Supply Pump Application - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

4.6

Application Selection

Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters
to values appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.
User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple
menus.
An Application Preset can either be selected from the Application Selection menu in the Setup Group
Setup Using the Setup Group on page
Note: 1. Application Presets can only be selected if all drive parameters are at their original default settings. It may be necessary to initialize the
drive by setting A1-03 to "2220" or "3330" prior to selecting an Application Preset.
2. Entering a value to A1-06 to enable an Application Preset will fix that value to the parameter. The value cannot be changed without first
setting A1-03 to 2220 or 3330 to initialize the drive.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter
A1-06 may automatically change the I/O terminal function from the default setting. Failure to comply may result in death or serious injury.
No.
A1-06
Application Presets
u

Setting 1: Water Supply Pump Application

No.
A1-02
Control Method Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-01
Duty Rating
E1-03
V/f Pattern Selection
E1-07
Mid Output Frequency
E1-08
Mid Output Frequency Voltage
L2-01
Momentary Power Loss Operation Selection
L3-04
Stall Prevention Selection during Deceleration
No.
b1-01
Frequency Reference Selection
b1-02
Run Command Selection
b1-04
Reverse Operation Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
E1-03
V/f Pattern Selection
E1-07
Mid Output Frequency
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
88) or in parameter A1-06. The following presets can be selected:
Parameter Name
Table 4.5 Water Supply Pump: Parameter Settings
Name
Table 4.6 Water Supply Pump: User Parameters (A2-01 to A2-16)
Parameter Name
Setting Range
0: Disabled
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC
5: Compressor
Default Setting
0: V/f Control
1: Reverse Prohibited
1.0 s
1.0 s
1: Normal Duty
0FH
30.0 Hz
50.0 V
1: Enabled
1: Enabled
No.
E1-08
Mid Output Frequency Voltage
E2-01
Motor Rated Current
Multi-Function Digital Input Terminal S5 Function
H1-05
Selection
Multi-Function Digital Input Terminal S6 Function
H1-06
Selection
Multi-Function Digital Input Terminal S7 Function
H1-07
Selection
L5-01
Number of Auto Restart Attempts

4.6 Application Selection

(Refer to Simplified
Default
0
Parameter Name
4
97