Application Selection - YASKAWA iQpump1000 User Manual

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

4.3 Application Selection

4.3
Application Selection
Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these Application
Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters to values
appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.
User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple
menus.
Note:
Entering a value to A1-03 to enable an Application Preset will fix that value to the parameter. The value cannot be changed without first
setting A1-03 to 2220 or 3330 to initialize the drive.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter
A1-03 may automatically change the I/O terminal function from the default setting. Failure to comply may result in death or serious injury.
No.
A1-03
Initialize Parameters
A1-06
Application Presets (monitor only)
<1> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
<2> Available in drive software versions PRG: 8553 and later. Not available in drive models 4A0930 and 4A1200.
138
Parameter Name
Settings
0: No initialization (default)
1110: User initialize (parameter values
must be stored using parameter o2-03)
2220: 2-Wire initialize
3330: 3-Wire initialize
5550: Terminal/Control initialize
6008: Pressure control
6009: Pump down level
6010: Geothermal mode
6011: VTC pressure control
6012: Pivot Panel VTC
6013: Advanced Pressure Control
6014: Pivot Panel Submersible
7770: General purpose
7771: Submersible motor control
0: Pressure Control
1: General Purpose
2: Sub Mtr GP Oper
5: General Ext HOA
6: General HOA Keys
8: Pressure Control
9: Pump Down Level
10: Geothermal Mode
11: VTC Pressure Control
12: Pivot Panel VTC
13: Advanced Pressure Control
14: Pivot Panel Submersible
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Default
0
<1>
<1>
<2>
<1>
<1>
0
<1>
<1>
<2>

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents