4.5 Application Selection

4.5

Application Selection

Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these Application
Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters to values
appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.
User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple
menus.
Note:
1. Application Presets can only be selected if all drive parameters are at their original default settings.
2. Entering a value to A1-03 to enable an Application Preset will fix that value to the parameter. The value cannot be changed without first
setting A1-03 to 2220 or 3330 to initialize the drive.
Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter
WARNING!
A1-03 may automatically change the I/O terminal function from the default setting. Failure to comply may result in death or serious injury.
No.
A1-03
Initialize Parameters
A1-06
Application Presets (monitor only)
<1>
Refer to Fan and Pump Application Presets on page 125
90
Parameter Name
for drive setup using A1-03 = 8008, 8009, 8010, or 8011.
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Settings
0: No initialization (default)
1110: User Initialize (parameter values
must be stored using parameter o2-03)
2220: 2-Wire Initialize
3330: 3-Wire Initialize
5550: Terminal/Control Initialize
<1>
8008: Pump
<1>
8009: Pump w/ PI
<1>
8010: Fan
<1>
8011: Fan w/ PI
0: Disabled
8: Pump
9: Pump w/ PI
10: Fan
11: Fan w/ PI
Default
0
0

Hide quick links: