i.3 Mechanical Installation

i.3

Mechanical Installation

This section outlines specifications, procedures, and environment for proper mechanical installation of the drive.
u
Installation Environment
Install the drive in an environment matching the specifications in
the drive.
Environment
Installation Area
Ambient Temperature
Humidity
Storage Temperature
Surrounding Area
Altitude
Vibration
Orientation
<1> Models 4A0930 and 4A1200 are rated at 5.9 m/s
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to erroneous
operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to comply
could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before
drive start-up, as the cover will reduce ventilation and cause the drive to overheat.
u
Installation Orientation and Spacing
NOTICE: Install the drive upright as illustrated in
NOTICE: Install the drive upright as specified in the manual. Failure to comply may damage the drive due to improper cooling.
14
Table i.1 Installation Environment
Indoors
-10 °C to +40 °C (IP20/NEMA 1, UL Type 1 enclosure)
-10 °C to +50 °C (IP00/Open Type enclosure)
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
-20 to +60 °C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
1000 m or lower, up to 3000 m with derating
2
10 to 20 Hz at 9.8 m/s
(32.15 ft/s
2
20 to 55 Hz at 5.9 m/s
(19.36 ft/s
2
2
2.0 m/s
(6.56 ft/s
) (Models 2A0250 to 2A0415, 4A0208 to 4A1200, and 5A0125 to 5A0242)
Install the drive vertically to maintain maximum cooling effects.
2
(19.36 ft/s
Figure
i.4. Failure to comply may damage the drive due to improper cooling.
Figure i.4 Correct Installation Orientation
Table i.1
to help prolong the optimum performance life of
Conditions
<1>
2
)
2
) (Models 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0099) or
2
)
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide