You enter the basic project settings for batches in this dialog. All adjustable settings are
arranged in groups. Click a property, and then select a setting in the "Value" column. You also
obtain descriptions for each selected property in a window below.
General > Allow online setpoint change
Specifies the default setting "Modifiable" for newly created parameters in the Recipe Editor.
If "Modifiable" is selected, changes to parameters (setpoints) of the control recipe are permitted
during batch control.
Default setting: Yes.
General > Allow deleting of completed, not archived batches
When you use this property, batches are deleted without "Close" and "Archive" beforehand.
The corresponding command is "Delete immediately" and requires the appropriate user
permission in BatchCC.
Default setting: No.
General > Transfer setpoint changes to active step
Specifies the default setting "Effective immediately" for newly created parameters in the Recipe
Editor.
With recipe phases of the type EPH and EOP, parameter values changed by the operator will
become effective immediately; this means they are transferred from the running recipe steps
(EPH and EOP) in the control recipe directly to the automation system where they effect the
block running in the AS. If you use the property, a setpoint change is applied immediately in
the AS. If the property is not enabled, a newly entered value is only saved, and then used the
next time the function is called.
Default setting: No.
General > Automatically delete archived batches
If you set this property to "Yes", batches that were previously archived are automatically
deleted from the corresponding order folder in BatchCC.
Default setting: No.
General > Use predefined batch name
If you set the value of this property to "Yes", the predefined settings for the batch name
assignment are used during batch creation.