BATCH Recipe Editor
10.4 Creating recipes
Tab
Product
Input material
Output material
Parameter
Process tags
Change log
ESIG
578
What is set or dis‐
Meaning/comment
played
Product, Quality
Settings for the main product
Product code
Unique numeric code for the project (e.g. an internal
command code) with which the product can be identi‐
fied.
Reference quantity
The reference quantity is meant for quantity scaling, this
means, the parameters in the recipe relate to this value
and they have to be adjusted in the event of discrepan‐
cies in the batch quantity.
Minimum scale, maxi‐
Limits the upper and lower limits of the batch quantity.
mum scale
In batch planning, the quantities specified are checked
to make sure they are not lower/higher than the values
entered here.
Material list
For the steps linked to EOPs, EPHs or the operator di‐
alogs, the entries are taken from the basic automation;
for a library reference from the library operation. New
materials can also be created. For each input material
configured, the material, quality, scaling function and
required quantity are specified.
Either concrete values (internal formula) or reference to
values of an external formula.
Material list
For the steps linked to EOPs, EPHs or the operator di‐
alogs, the entries are taken from the basic automation;
for a library reference from the library operation. New
materials can also be created. For each output material
configured, the material, quality, scaling function and
required quantity are specified.
Either concrete values (internal formula) or reference to
values of an external formula.
Parameter list
For the steps linked to EOPs, EPHs or the operator di‐
alogs, the parameters are taken from the basic automa‐
tion; for a library reference from the library operation.
New parameters of the type real, bool, integer, string
and enumeration can also be created.
Either concrete values (internal formula) or reference to
values of an external formula.
Measured variables
Measured variables for the batch report:
that will be logged
You can select measured variables for archiving. As
measured variables, the process values of the parame‐
ter blocks (EPAR_) linked with the EOP, EPH and
TAG_COLL blocks are available.
List of modifications
List in which the modifications made to the recipe are
documented.
Electronic signature
Specifying electronic signatures in compliance with
FDA or 21 CFR Part 11:
The "electronic signatures" function allows the operator
to enter one or more signatures in the form of dialogs
similar to the logon prompts normal in Windows when
operator input is made to recipes, recipe steps etc.