BATCH Control Center
9.2 Specifying user permissions
permissions necessary for their tasks. This should help you to assign your various user roles
with the appropriate individual permissions for their function. Please note that individual
permissions can be assigned to multiple function groups. Each individual permission in a
function group is linked to the Individual permissions chapter.
In the third chapter, "Roles", all individual permissions are assigned to various roles. These
roles correspond to the roles specified on the "Individual permissions" tab in the "Permission
management" dialog. It is possible to assign an individual permission to multiple roles in this
view also. Similarly, you have the option to link each individual permission to its description.
The fourth chapter, "All computers", presents information from the Permission management
dialog, "Computers and units" tab, in the BCC. You are shown which role is logged in on which
PC. The computer name is displayed. Every role shown is listed as a link, referencing the
corresponding role and the individual permissions.
The fifth chapter, "Units", presents information from the "Computers and units" tab in the
Permission management dialog. You are shown which role is logged in on which unit. Every
role shown is listed as a link, referencing the corresponding role and the individual permissions.
9.2.6

Setting up the emergency operator

Automatic logon of standard user or emergency operator
You can set up an emergency operator in SIMATIC BATCH using SIMATIC Logon. When a
logged-on user logs off in BatchCC, the specified user is automatically logged on as an
emergency operator in BatchCC. This ensures that the system can be operated at all times.
You create a new role named "Emergency_Operator" in BatchCC for this function and
administer the rights of this user group. The user logged on as an emergency operator cannot
log off in BatchCC.
Requirements
● You are using SIMATIC Logon.
● You have the necessary permissions in BatchCC and for SIMATIC Logon to make the
configuration.
Procedure
1. Open the "Configure SIMATIC Logon" dialog by selecting Start > SIMATIC > SIMATIC
Logon > Configure SIMATIC Logon.
2. Select the check box "Use the following data if the user is not explicitly logged on" in the
"Configure SIMATIC Logon" dialog, "General" tab.
3. Enter a name in the "Group" text box. For "User", enter the name of an emergency operator.
The name of the emergency operator specified here appears in BatchCC as a user who is
logged on.
4. Close the dialog with "OK".
288