Monitoring time
It is not possible to enter a monitoring time for the command step and the input box is always
grayed out. The execution of commands for recipe procedure elements cannot be monitored.
The command step cannot wait until all commands have executed.
Scaling the runtime
You use scaling functions (Page 579) to make processes quantity-dependent. Depending on
the specific quantity of the batch, the duration of a step is also corrected via the set scaling
function. By default, "linear" and "quadratic" scaling functions are available for selection. The
scaling involves both the runtime and monitoring time.
14.1.9.19

"General" tab (Library operation unit class properties)

Name and version
You specify the name and version of the library operation when you create a new library
operation or when you Save as.... The name cannot be modified in this tab.
Status:
The status provides you with information on the status of the library operation:
● In progress: Initial status of a newly created or copied library operation.
● Released for testing: Library operations that have been released for testing can be used
for creating a batch for test purposes.
● Released for production: This status shows that the library operation tested for production
is provided.
● Testing release: This status indicates that the system is currently checking for errors
following a process cell update (validation).
● Release revoked: This status indicates that the library operation must no longer be used
for new batches.
● Release invalid: This status shows that the test of the library operation was not successful
when updating the process cell data. In this status you can edit and release the library
operation.
● Unknown: Status of a library operation unknown. An error may have occurred when creating
the library operation. Delete this library operation or open it again so that the library
operation changes to the "In progress" status.
Unit class:
The unit class selected in the "Allocation" tab of the library operation is displayed.
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA