14.1 Dialogs
Properties
Name of the object selected in the process cell tree.
Description
Predecessor/successor
Available
Runtime name
CFC chart
"Open" button
Not possible in the multi‐
project.
Connection UNIT_NAME
Unit
Button
Compile
This button only exists for a
project and not for a multipro‐
ject.
Log
Not possible in the multiproject
"Errors" display field
"Warnings" display field
"Display" button
914
The description of the unit is displayed in this text box. You enter description
texts in the object properties for the unit in SIMATIC Manager.
This is where the predecessor or successor (unit) assigned in the plant
hierarchy of the unit properties on the "ISA-88 type definition" tab is dis‐
played.
If you have activated the "Unit available for batches" option in the properties
dialog of the unit in the plant hierarchy, then there is a tick in the option box.
If the option is not used then there is no tick in the options box.
The runtime name is automatically during compiling/merging of the batch
instances and displayed here. It corresponds to the WinCC tag name plus
the OS name as prefix.
The name of the CFC chart configured for the unit is displayed here.
Click on the "Open" button to open the appropriate CFC chart and select
the block.
If you have specified an identifier for the UNIT_NAME parameter of the
UNIT_BLOCK block, it is displayed here and used in the subsequent recipe
creation. If no identifier was specified for this parameter, the entry is empty
and the name of the hierarchy folder is used in the subsequent recipe cre‐
ation. The reason for this is that the identifiers of hierarchy folders in the
PH often have a naming scheme and a unit name cannot therefore be freely
selected. To make this possible however, the UNIT_NAME parameter can
be used in the UNIT_BLOCK block.
All batch instance blocks of the CFC chart of the selected object are
read in. This also implicitly involves a check for consistency with the
batch types and conformity to ISA-88.
The number of errors for the selected log is displayed.
The number of warnings for the selected log is displayed.
The logging is activated with the "Display" button. The selected log is
generated as an XML file in the specified layout and displayed in In‐
ternet Explorer.
Select "Process cell" and click the "Display" button to show all process
cell errors or warnings. You can also right-click a selected object and
select the "Display log" function to display object-specific errors or
warnings.