only performed when you specify a time not equal to 0. You cannot set a value less than 15
seconds.
Additional information: Communication monitoring (Page 208)
Units
If you select the check box, all text entries (batch name, batch ID, product, product version,
recipe, recipe version, as well as formula) in the "UNIT_PLC" block and in the corresponding
faceplate are deleted when the corresponding unit has been released.
If you clear the check box, only the text entries (batch name and batch ID) are deleted in the
block and in the "UNIT_PLC" faceplate. All other text entries remain intact when the appropriate
unit has been released.
Deactivate batch data management (CDV)
If you select the check box, the BATCH component "CDV" is deactivated. With this setting,
BATCH messages and process values are not collected by the CDV. This data is missing in
reports and archives. A corresponding note is output in the print preview and in the batch
report. This setting is not changed over during operation. Download the change in the BATCH
engineering to the BATCH server in the BATCH configuration dialog. Stop BATCH Runtime
and the BATCH project in the BATCH Launch Coordinator. Then, restart the project and
Runtime.
The check box is cleared by default.
Message language
Select the language in which the batch data management (CDV) will collect the BATCH
messages from a drop-down list box.
Downloading a batch process cell
If you select the check box, you can download the BATCH process cell to the BATCH server
despite changes in the basic engineering (SFC and CFC) that have not been compiled and
downloaded to the AS.
The check box is cleared by default. This means that downloading the batch process cell is
only possible if you have also compiled and downloaded the current data from the basic
engineering to the AS.
14.1.12.61

"Process cells" tab

Introduction
This tab is only available for a multiproject.
The dialog is used to display process cell names, and if the names do not agree, then to make
a necessary name adaptation. Due to the SIMATIC BATCH configuration guidelines it is
SIMATIC BATCH V8.2