Supplemental Information About Online Assignment Of A Unit For Flat Recipes; Inserting And Labeling Recipe Elements; Recipe Procedural Element (Insert Menu) - Siemens SIMATIC BATCH Operating Manual

Process control system pcs 7
Table of Contents

Advertisement

BATCH Recipe Editor
10.4 Creating recipes
10.4.4.7

Supplemental information about online assignment of a unit for flat recipes

Online assignment of several recipe phases with the same unit assignment
If several recipe phases are in a flat recipe with the same unit assignment, the online
assignment is only performed for the first recipe phase.
For safety reasons the assigned unit is retained for all subsequent recipe phases, even when
the unit is released upon completion of a phase.
Repeated online assignment
To repeat an online assignment, a completed or aborted recipe phase needs to be reset. None
of the other recipe phases with the same unit assignment can be active in this case.
Recommendation
To be able to repeat an online assignment in a flat recipe, recipe phases should be distributed
over many different unit assignments when the recipe is originally created.
10.4.5

Inserting and labeling recipe elements

10.4.5.1

Recipe procedural element (Insert menu)

Overview
With this function, you insert recipe steps of the type recipe procedure element within a recipe.
This step element is a substitute object for the steps and step sequences stored within the
nested hierarchy level.
● Hierarchical recipe: RUP, ROP, RPH
● Flat recipe Substructure
Open or double-click
The window for editing the recipe steps or step sequences in the nested hierarchy level opens
for the selected object.
532
SIMATIC BATCH V8.2
Operating Manual, 02/2016, A5E35958174-AA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents