14.1 Dialogs
14.1.12.20

"Phase type_EPH" selection

Phase type selection
You have selected the "Phase type_EPH" object in the "Process cell data" list.
Runtime name in the dialog header
Display of the runtime name.
Process cell data
For navigation in the process cell data
Properties
Name of the object selected in the process cell tree.
Description
Allow operator instruc‐
tion:
V blocks
Default instance
886
The description of the phase type is entered or displayed in this text box.
With this option, you specify whether or not this phase can be used by an
operator instruction.
Indicates the version of the phase type used. The following block types are
available for selection in the drop-down list box:
AF24: The block has 24 parameters.
AF12: The block has 12 parameters.
AF6: The block has 6 parameters.
AF16S: The block has 16 parameters.
Using Batch block instances of different versions (EOP, IEOP, SFC-TYPE )
but the same phase type automatically results in so-called mixed operation.
However mixed operation is permitted exclusively for combinations of ver‐
sions 5, 6i, and SFC type. Mixed operation of version V4.02 with other
versions is not allowed.
Allowed versions / combinations are:
Version = 4.02
Version = V5
Version = V6i
Version = V6
Mixed version = V5 / V6i
Mixed version = V5 / V6
Mixed version = V6i / V6
Mixed version = V5 / V6i / V6
If at least two block instances of an SFC type are configured within the plant
hierarchy, the row is displayed. If multiple block instances are deleted, the
row disappears again.
Select one of the possible block instance names from the drop-down list.
The selected default instance is given preference when creating recipes.