Siemens SIMATIC BATCH Operating Manual page 984

Process control system pcs 7
Table of Contents

Advertisement

Context help references
14.1 Dialogs
Button: Data type
Assigned unit of measure Assign the physical unit of measure to the operation type parameter here.
Button: Unit of measure
Archive measured value
Test manufacturing in‐
struction
Control strategy parame‐
ter
Button: Edit
Events log ID
Created by
Parameters
Buttons
Update
Delete
984
Activating this button takes you to the appropriate batch data type. Use the
Back button on the batch data type to return to this point.
You must specify desired units of measure beforehand under "Units of
measure".
Activating this button takes you to the appropriate unit of measure. Use the
Back button on the unit of measure to return to this point.
An operation type parameter is selected here if a connection to a WinCC
process tag is to be established. This selection is the prerequisite for as‐
signing a type parameter to process tag archive tag. You make this assign‐
ment subsequently on the instance parameter of the appropriate phase
type.
An operation type parameter is selected here if it is to be provided in the
batch log for the manual check (manufacturing instruction).
Select the option if the type parameter is to be a control strategy.
This button opens a subsequent dialog. You assign the setpoints of the
operation to the individual control strategies here.
Here you can specify a value from 0 - 65535 that can be evaluated later in
a user batch log to allow filtering. Different values are permitted for setpoint
and process value. This means, for example, that you could filter according
to setpoints with setpoint ID ≤ 1000 AND setpoint ID ≥ 500 and for process
values with process value ID ≤ 2000. The user can specify how convenient
such a query is in his log software.
Specification of the application that created the object, either SIMATIC
BATCH PCell Control Center or SIMATIC Manager:
● If a type object was created by SIMATIC Manager, additional subobjects
cannot be added, nor can the selected object be deleted or changed,
either via the PCC API or with the PCC configuration dialog.
● If an instance object was created by SIMATIC Manager, additional
subobjects can be added via the PCC API or with the PCC configuration
dialog. However, it is still not possible to delete or change the selected
object here.
All batch instances are adapted according to the batch types. This action
is always required if a change has been made to batch types of existing
batch instances (e.g., inserting a new parameter, changing the unit of
measure, etc.).
The operation type parameters object can be deleted here. Deletion is only
possible if the selected object is not in use.