9.1 Starting and operating
9.1.4.4

Customization of the properties dialogs for RPEs

Which tabs are displayed in the properties dialogs of all recipe procedure elements (RPEs) in
the recipe editor is set in the project settings in the "Display" folder in the tabs for recipe editing.
The default setting is always to display all tabs in the dialogs. The settings apply only to the
dialogs in the recipe editor and for online structural changes. In process mode, all tabs are still
displayed in the dialogs.
System response when tabs are hidden
If you hide tabs, please note the following system response:
● If tabs are hidden in the recipe editor although they contain parameters, for example in the
Transfer parameters tab, you can still query these parameters in the transition conditions
in process mode and they are also listed in the batch log. The system always handles
parameters of hidden tabs as being present, for example when importing master recipes
and these are always taken into account in during validation. The system does not generate
any specific error messages relating to this. The following tabs are affected by this
functionality:
– Transfer parameters
– Process parameters
– Input material
– Output material
● If tabs are hidden in the recipe editor although they contain electronic signatures and/or
synchronizations, these are taken into account fully when importing, however their
functionality is disabled in process mode. The configured functionality is listed in the batch
report. The following tabs are affected by this functionality:
– Electronic signature
– Synchronization
9.1.4.5

Properties dialogs in BatchCC, viewer and OS controls

System response in BatchCC and viewer for archived batches
Since there is no specific project setting for the BatchCC and the viewer for displaying or hiding
tabs in the properties dialogs, tabs are always displayed if they include configuration settings,
for example an electronic signature or transfer parameters. This means that tabs are hidden
if they do not contain any configuration settings. This behavior applies to the following tabs:
● Transfer parameters
● Process parameters
● Input material
● Output material
● Electronic signature
● Synchronization