Siemens SIMATIC BATCH Operating Manual page 430

Process control system pcs 7
Table of Contents

Advertisement

BATCH Control Center
9.8 Batch control
Possible status (basic status) of recipe procedure elements (RPEs)
Status
RPE_STATE_UNDEFINED
RPE_STATE_EDITED
RPE_STATE_IDLE
RPE_STATE_STARTING
RPE_STATE_RUNNING
RPE_STATE_READY
RPE_STATE_COMPLETING
RPE_STATE_COMPLETED
RPE_STATE_CONTINUOUS
RPE_STATE_ABORTED
RPE_STATE_ABORTING
RPE_STATE_STOPPED
RPE_STATE_STOPPING
RPE_STATE_HELD
RPE_STATE_HOLDING
RPE_STATE_RESUMING
RPE_STATE_PAUSED
RPE_STATE_PAUSING
RPE_STATE_SOFT_STOPPED
RPE_STATE_SOFT_STOPPING
Note
If a unit recipe contains ROP steps or substructure steps in "continuous operation" state, the
Continuous symbol is always displayed in the control recipe view, regardless of the respective
basic status. The Continuous symbol is not displayed if a recipe phase was configured for
continuous operation but has not yet reached this status.
Possible expanded status of recipe procedure elements (RPEs)
Status
RPE_EXSTATE_0
RPE_EXSTATE_ERROR
RPE_EXSTATE_FOCUS
RPE_EXSTATE_CMD_PROCESSING
RPE_EXSTATE_BREAKPOINT
RPE_EXSTATE_UNIT_ALLOCATING
RPE_EXSTATE_UNIT_ALLOCATED
430
Value, deci‐
Description
mal
0
Undefined
1
Edited
2
Idle
3
Starting
4
Running
5
Ready to complete
6
Completing
7
Completed
8
Continuous
9
Aborted
10
Aborting
11
Stopped
12
Stopping
13
Held
14
Holding
15
Resuming
16
Paused after step
17
Pausing after step
18
Stopped except for continuous
19
Stopping except for continuous
Value, hexa‐
Value, decimal
decimal
0x0
0
0x1
1
0x2
2
0x4
4
0x8
8
0x10
16
0x20
32
Operating Manual, 02/2016, A5E35958174-AA
Description
Initial value
Error
Edit flag set
Command processing active
Breakpoint
Waiting for allocation of the unit
Unit allocated
SIMATIC BATCH V8.2