WAGO-I/O-SYSTEM 750
750-354/000-001 EtherCAT® Fieldbus Coupler, ID Switch
11.2.5.17 Vibration Velocity/Bearing Condition Monitoring VIB I/O
750-645
The Vibration Velocity/Bearing Condition Monitoring VIB I/O has a total of 12
bytes of user data in both the Input and Output Process Image (8 bytes of
module data and 4 bytes of control/status). The following table illustrates the
Input and Output Process Image, which have 8 words mapped into each image.
Word alignment is applied.
Table 173: Vibration Velocity/Bearing Condition Monitoring VIB I/O 750-645
Input and Output Process Image
Offset
0
1
2
3
4
5
6
7
11.2.5.18 AS-interface Master Module
750-655,
753-655
The length of the process image of the AS-interface master module can be set to
fixed sizes of 12, 20, 24, 32, 40 or 48 bytes.
It consists of a control or status byte, a mailbox with a size of 0, 6, 10, 12 or 18
bytes and the AS-interface process data, which can range from 0 to 46 bytes.
The AS-interface master module has a total of 6 to maximally 24 words data in
both the Input and Output Process Image. Word alignment is applied.
The first Input and output word, which is assigned to an AS-interface master
module, contains the status / control byte and one empty byte.
Subsequently the mailbox data are mapped, when the mailbox is permanently
superimposed (Mode 1).
Byte Destination
High Byte
Low Byte
-
D1
-
D3
-
D5
-
D7
C0/S0
not used
D0
(log. Channel 1, Sensor input 1)
C1/S1
not used
D2
(log. Channel 2, Sensor input 2)
C2/S2
not used
D4
(log. Channel 3, Sensor input 3)
C3/S3
not used
D6
(log. Channel 4, Sensor input 2)
I/O Modules 185
Description
Control/status byte
(log. Channel 1,
Sensor input 1)
Data bytes
Control/status byte
(log. Channel 2,
Sensor input 2)
Data bytes
Control/status byte
(log. Channel 3,
Sensor input 1)
Data bytes
Control/status byte
(log. Channel 4,
Sensor input 2)
Data bytes
Manual