82 •
PROFINET IO 750-370
Process Image
3.1.5.2.5.2

Pulse Width Output Module

Two module types exist for the PWM output module:
Type of module
PWM output modules receive the consumer status (IOCS) from the I/O
controller and supply it with the provider status (IOPS) of the existing output
information in case only the actual user data is replaced. If all existing
information in the input and output image is made available then the process
data qualifier is additionally transmitted in the opposite direction.
The following table shows a list of the number of bytes for the individual
modules that are allocated in the respective process image (PA) and the
telegrams (TLG) in the direction of transmission and reception (Tx, Rx).
Type
Type
Description
PWM
2-Channel PWM output module,
16-Bit signed process value per
signal channel
PWM_EM
2-channel PWM output module,
16 Bit input and output data plus
control and status byte per signal
channel, access to the register
structure using cyclic data
exchange
Module
Data length [Byte]
PA
E
A
Tx
PWM
4
-
5
Module
Data length [Byte]
PA
E
A
Tx
PWM_EM
6
6
7
75x-511
2PWM
TLG
E
Rx
1
-
75x-511 2PWM, EM
TLG
E
Rx
7
U8,I16
Substitute I/O modules
75x-511
Data object
INST
A
-
I16
Data object
INST
A
2
U8,I16
WAGO-I/O-SYSTEM 750
PROFINET IO
INST
2
INST
2