VLT® AutomationDrive EZ FC 321
Programming Guide
Main menu mode
Quick menu mode
Main menu provides access to all parameters.
Quick menu takes the user through a few parameters, making it possible to start operating the drive. Change a parameter in either
main menu mode or quick menu mode.

3.1.6 Quick Menu Key Functions

Press [Quick Menu] to enter a list of different areas contained in the Quick Menu.
0RPM
0.00A
Quick Menus
Q1 My Personal Menu
Q2 Quick Setup
Q4 Smart Setup
Q5 Changes Made
Illustration 15: Quick Menus
Select Q1 My Personal Menu to show the selected personal parameters. These parameters are selected in parameter 0-25 My Personal
Menu. Up to 50 different parameters can be added in this menu.
Select Q2 Quick Setup to go through a selection of parameters to get the motor running almost optimally. The default settings for
the other parameters consider the required control functions and the configuration of signal inputs/outputs (control terminals).
The parameter selection is effected with the navigation keys. The parameters in the following table are accessible.
Table 7: Selection of Parameter
Parameter
Parameter 0-01 Language
Parameter 1-20 Motor Power [kW]
Parameter 1-22 Motor Voltage
Parameter 1-23 Motor Frequency
Parameter 1-24 Motor Current
Parameter 1-25 Motor Nominal Speed
Parameter 3-02 Minimum Reference
Select Changes made to get information about:
The last 10 changes. Use the [▵] [▿] navigation keys to scroll between the last 10 changed parameters.
The changes made since default setting.
Select Loggings to get information about the shown line readouts. The information is shown as graphs. Only parameters selected in
parameter 0-20 Display Line 1.1 Small and parameter 0-24 Display Line 3 Large can be viewed. It is possible to store up to 120 samples
in the memory for later reference.

3.1.7 Initial Commissioning

The easiest way of carrying out the initial commissioning is by pressing [Quick Menu] and following the quick set-up procedure
using LCP 102 (read the following table from left to right). The example applies to open-loop applications.
26 | Danfoss A/S © 2021.08
1(1)
How to Program
Setting
[kW]
[V]
[Hz]
[A]
[RPM]
[RPM]
AU373327181955en-000101 / 130R1208