VLT® AutomationDrive EZ FC 321
Programming Guide
Option
Name
[0]
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torque related to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max out freq
[119]
Torque % lim
Parameter 5-62 Pulse Output Max Freq #27
Table 329: Parameter 5-62 Pulse Output Max Freq #27
5-62 Pulse Output Max Freq #27
Default value: Size related
Conversion index: 0
Set the maximum frequency for terminal 27 corresponding to the output variable selected in parameter 5-60 Terminal 27 Pulse Out-
put Variable.
Parameter 5-63 Terminal 29 Pulse Output Variable
Table 330: Parameter 5-63 Terminal 29 Pulse Output Variable
5-63 Terminal 29 Pulse Output Variable
Default value: Size related
Conversion index: –
Option
Name
[0]
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[100]
Output frequency
[101]
Reference
[102]
Feedback
174 | Danfoss A/S © 2021.08
Description
Select the display output for terminal 27.
Parameter type: Range, 0 - 32000 Hz
Data type: Uint32
Parameter type: Option
Data type: Uint8
Description
Select the display output for terminal 29.
Parameter Descriptions
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
AU373327181955en-000101 / 130R1208