Parameter 8-31 Address
Table 423: Parameter 8-31 Address
8-31 Address
Default value: 1
Conversion index: 0
Enter the address for the drive (standard) port. Valid range: Depends on the selected protocol.
Parameter 8-32 FC Port Baud Rate
Table 424: Parameter 8-32 FC Port Baud Rate
8-32 FC Port Baud Rate
Default value: Size related
Conversion index: –
Option
Name
[0]
2400 Baud
[1]
4800 Baud
[2]
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
Parameter 8-33 Parity/Stop Bits
Table 425: Parameter 8-33 Parity/Stop Bits
8-33 Parity/Stop Bits
Default value: [0] Even parity, 1 stop bit
Conversion index: –
Option
Name
[0]*
Even parity, 1 stop bit
[1]
Odd parity, 1 stop bit
[2]
No parity, 1 stop bit
[3]
No parity, 2 stop bits
214 | Danfoss A/S © 2021.08
Name
FC
FC MC
Modbus RTU
Parameter type: Range, 1 - 247
Data type: Uint8
Parameter type: Option
Data type: Uint8
Description
Baud rate selection for the FC (standard) port.
Parameter type: Option
Data type: Uint8
Parameter Descriptions
Description
Setup: 1 setup
Change during operation: True
Setup: 1 setup
Change during operation: True
Setup: 1 setup
Change during operation: True