Parameter 7-57 Process PID Fb. Filter Time
Table 408: Parameter 7-57 Process PID Fb. Filter Time
7-57 Process PID Fb. Filter Time
Default value: 0.001 s
Conversion index: -3
Set a time constant for the feedback first-order low-pass filter. The low-pass filter improves steady-state performance and dampens
oscillations on the reference/ feedback signals. However, severe filtering can be detrimental to dynamic performance.
4.9 Parameter Group 8-** Communications and Options
4.9.1 8-0* General Settings
Parameter 8-01 Control Site
Table 409: Parameter 8-01 Control Site
8-01 Control Site
Default value: [0] Digital and ctrl. word
Conversion index: –
The setting in this parameter overrides the settings in parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select.
Option
Name
[0]*
Digital and ctrl.word
[1]
Digital only
[2]
Controlword only
Parameter 8-02 Control Word Source
Table 410: Parameter 8-02 Control Word Source
8-02 Control Word Source
Default value: Size related
Conversion index: –
This parameter cannot be adjusted while the motor is running.
Select the source of the control word: 1 of 2 serial interfaces or 4 installed options. During initial power-up, the drive automatically
sets this parameter to [3] Option A if it detects a valid fieldbus option installed in slot A. When the option is removed, the drive
detects a configuration change, sets parameter 8-02 Control Word Source to default setting [1] FC RS485, and trips. If an option is
installed after initial power-up, the setting of parameter 8-02 Control Word Source does not change, but the drive trips and shows:
Alarm 67, Option Changed. When retrofitting a bus option into a drive that did not have a bus option installed earlier, change the
control to bus-based. This change is required for safety reasons to avoid an unintended change.
Option
Name
Description
[0]
None
[1]
FC RS485
[2]
FC USB
Danfoss A/S © 2021.08
Parameter type: Range, 0.001 - 1 s
Data type: Uint16
Parameter type: Option
Data type: Uint8
Description
Use both digital input and control word.
Use digital inputs only.
Use control word only.
Parameter type: Option
Data type: Uint8
N O T I C E
Parameter Descriptions
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
AU373327181955en-000101 / 130R1208 | 203