Parameter 3-90 Step Size
Table 217: Parameter 3-90 Step Size
3-90 Step Size
Default value: 0.1%
Conversion index: -2
Enter the increment size required for increase/decrease as a percentage of the synchronous motor speed, n
activated, the resulting reference is increased or decreased by the value set in this parameter.
Parameter 3-91 Ramp Time
Table 218: Parameter 3-91 Ramp Time
3-91 Ramp Time
Default value: 0 s
Conversion index: -2
Enter the ramp time, that is the time for adjustment of the reference 0–100% of the specified digital potentiometer function (in-
crease, decrease, or clear). If increase/decrease is activated for longer than the ramp delay period specified in parameter 3-95 Ramp
Delay, the actual reference is ramped up/down according to this ramp time. The ramp time is defined as the time used to adjust the
reference by the step size specified in parameter 3-90 Step Size.
Parameter 3-92 Power Restore
Table 219: Parameter 3-92 Power Restore
3-92 Power Restore
Default value: [0] Off
Conversion index: –
Option
Name
Description
[0]*
Off
Resets the digital potentiometer reference to 0% after power-up.
[1]
On
Restores the most recent digital potentiometer reference at power-up.
Parameter 3-93 Maximum Limit
Table 220: Parameter 3-93 Maximum Limit
3-93 Maximum Limit
Default value: 100%
Conversion index: 0
Set the maximum allowed value for the resulting reference. This is recommended if the digital potentiometer is used for fine-tuning
of the resulting reference.
Parameter 3-94 Minimum Limit
Table 221: Parameter 3-94 Minimum Limit
3-94 Minimum Limit
Default value: 100%
Conversion index: 0
Set the minimum allowed value for the resulting reference. This is recommended if the digital potentiometer is used for fine-tuning
of the resulting reference.
122 | Danfoss A/S © 2021.08
Parameter type: Range, 0.01 - 200%
Data type: Uint16
Parameter type: Range, 0 - 3600 s
Data type: Uint32
Parameter type: Option
Data type: Uint8
Parameter type: Range, -200 - 200%
Data type: Int16
Parameter type: Range, -200 - 200%
Data type: Int16
Parameter Descriptions
Setup: All setups
Change during operation: True
. If increase/decrease is
s
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
AU373327181955en-000101 / 130R1208