VLT® AutomationDrive EZ FC 321
Programming Guide
Parameter 30-27 Light Load Speed [%]
Table 713: Parameter 30-27 Light Load Speed [%]
30-27 Light Load Speed [%]
Default Value: 0%
Conversion Index: 0
Use this parameter when the light-load detection is active to define the speed during current measurement. Enter the reference
speed during the light-load detection. The value is a percentage of nominal motor speed in parameter 1-25 Motor Nominal Speed.
For standard asynchronous motors, the synchronous speed is used instead of parameter 1-25 Motor Nominal Speed due to slip.
Parameter 30-28 Evacuation Speed [%]
Table 714: Parameter 30-28 Evacuation Speed [%]
30-28 Evacuation Speed [%]
Default Value: 0%
Conversion Index: 0
Speed for evacuation after detection of light-load direction.
Parameter 30-29 Ramp Time
Table 715: Parameter 30-29 Ramp Time
30-29 Ramp Time
Default Value: Size related
Conversion Index: -2
Ramp times during evacuation and measurement sequences.
4.20.3 30-5* Unit Configuration
Parameters in this group allow to configure the operation of internal units that communicate with the drive. The settings affect the
behavior of hardware components inside the drive.
Parameter 30-50 Heat Sink Fan Mode
Table 716: Parameter 30-50 Heat Sink Fan Mode
30-50 Heat Sink Fan Mode
Default Value: Size related
Conversion Index: -
Select how the heat sink fan responds to operating conditions. Use parameter 14-52 Fan Control to control the minimum fan speed.
Option
Name
[0]
Simple profile
[1]
Reduced acoustics
[2]
Standard
[3]
Cooler operation
Danfoss A/S © 2021.08
Parameter Type: Range, 0 - 100%
Data Type: Uint16
Parameter Type: Range, 0 - 100%
Data Type: Uint16
Parameter Type: Range, 0.01 - 3600 s
Data Type: Uint32
Parameter Type: Option
Data Type: Uint8
Description
The simple profile is a passive fan control based on the current temperature state of the drive. This
option represents the classic operating behavior of fans.
Parameter Descriptions
Setup: All set-ups
Change during operation: True
Setup: All set-ups
Change during operation: True
Setup: All set-ups
Change during operation: True
Setup: 2 set-ups
Change during operation: True
AU373327181955en-000101 / 130R1208 | 339