Parameter 1-25 Motor Nominal Speed
Table 82: Parameter 1-25 Motor Nominal Speed
1-25 Motor Nominal Speed
Default value: Size related
Conversion index: 67
Enter the nominal motor speed value from the motor nameplate data. The data is used for calculating motor compensations.
n
= n
− n
m, n
s
slip
Parameter 1-26 Motor Cont. Rated Torque
Table 83: Parameter 1-26 Motor Cont. Rated Torque
1-26 Motor Cont. Rated Torque
Default value: Size related
Conversion index: -1
Enter the value from the motor nameplate data. The default value corresponds to the nominal rated output. This parameter is avail-
able when parameter 1-10 Motor Construction is set to [1] PM, non-salient SPM, that is, the parameter is valid for PM and non-salient
SPM motors only.
Parameter 1-29 Automatic Motor Adaptation
Table 84: Parameter 1-29 Automatic Motor Adaptation (AMA)
1-29 Automatic Motor Adaptation (AMA)
Default value: [0] Off
Conversion index: –
This parameter cannot be adjsuted while the motor is running.
The AMA function optimizes dynamic motor performance by automatically optimizing the advanced motor parameters (parameter
1-30 Stator Resistance (Rs) to parameter 1-35 Main Reactance (Xh)) at motor standstill. Activate the AMA function by pressing [Hand
On] after selecting [1] Enable Complete AMA or [2] Enable Reduced AMA. See also the section Automatic Motor Adaptation in the De-
sign Guide. After a normal sequence, the display reads: Press [OK] to finish AMA. After pressing [OK], the drive is ready for operation.
Ensure that a value is set in parameter 14-43 Motor Cosphi before running AMA II.
Op-
Name
Description
tion
[0]*
Off
[1]
Enable
Performs
complete
•
AMA of the stator resistance R
AMA
•
The rotor resistance R
•
The stator leakage reactance X
•
The rotor leakage reactance X
•
The main reactance X
68 | Danfoss A/S © 2021.08
Parameter type: Range, 10 - 60000 RPM
Data type: Uint16
Parameter type: Range, 0.1 - 100000.0 Nm
Data type: Uint32
Parameter type: Option
Data type: Uint8
N O T I C E
N O T I C E
s
r
1
, and
2
h
Parameter Descriptions
Setup: All setups
Change during operation: False
Setup: All setups
Change during operation: False
Setup: All setups
Change during operation: False
AU373327181955en-000101 / 130R1208