VLT® AutomationDrive EZ FC 321
Programming Guide
Option
Name
[1843]
Analog out X49/7
[1844]
Analog out X49/9
[1845]
Analog out X49/11
[1846]
X49 digital output [bin]
[1860]
Digital input 2
[3110]
Bypass status word
[3466]
SPI error counter
Parameter 15-11 Logging Interval
Table 530: Parameter 15-11 Logging Interval
15-11 Logging Interval
Default Value: Size related
Conversion Index: -3
Enter the interval in ms between each sampling of the variables to be logged.
Parameter 15-12 Trigger Event
Table 531: Parameter 15-12 Trigger Event
15-12 Trigger Event
Default Value: [0] False
Conversion Index: -
Select the trigger event. When the trigger event occurs, a window is applied to freeze the log. The log then retains a specified per-
centage of samples before the occurrence of the trigger event (parameter 15-14 Samples Before Trigger).
Option
[0]*
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
288 | Danfoss A/S © 2021.08
Parameter Type: Range, 0.000 - 0.000
Data Type: Time diff wo DateID [4]
Parameter Type: Option
Data Type: Uint8
Name
False
True
Running
In range
On reference
Torque limit
Current limit
Out of current range
Below I low
Above I high
Out of speed range
Below speed low
Parameter Descriptions
Description
Setup: 2 set-ups
Change during operation: True
Setup: 1 set-up
Change during operation: True
Description
AU373327181955en-000101 / 130R1208
Need help?
Do you have a question about the VLT AutomationDrive EZ FC 321 and is the answer not in the manual?