VLT® AutomationDrive EZ FC 321
Programming Guide
The drive has no back-up of the clock function. The set date/time is reset to default (2000-01-01 00:00) after a power-down. In
parameter 0-79 Clock Fault, it is possible to program a warning if the clock has not been set properly, for example after a power-
down. Set the time at least 1 hour later than actual time.
Parameter 23-15 Reset Maintenance Word
Table 690: Parameter 23-15 Reset Maintenance Word
23-15 Reset Maintenance Word
Default Value: [0] Do not reset
Conversion Index: -
When messages are reset, maintenance item, action, and maintenance date/time are not canceled. Parameter 23-12 Maintenance
Time Base is set to [0] Disabled.
Set this parameter to [1] Do reset to reset the maintenance word in parameter 16-96 Maintenance Word and reset the message shown
in the LCP. This parameter changes back to [0] Do not reset when pressing [OK].
Option
[0]*
[1]
Parameter 23-16 Maintenance Text
Table 691: Parameter 23-16 Maintenance Text
23-16 Maintenance Text
Default Value: 0
Conversion Index: 0
6 individual texts (Maintenance Text 0...Maintenance Text 5) can be written for use in either parameter 23-10 Maintenance Item or
parameter 23-11 Maintenance Action. The text is written according to the guidelines in parameter 0-37 Display Text 1.
Parameter 23-18 Reset Mechanical Brake Counter
Table 692: Parameter 23-18 Reset Mechanical Brake Counter
23-18 Reset Mechanical Brake Counter
Default Value: [0] Do not reset
Conversion Index: -
Option
Name
Description
[0]*
Do not reset
Select this option to disable the reset of the mechanical brake counter.
[1]
Do reset
Select this option to enable the reset of the mechanical brake counter. After resetting the mechanical
brake counter, the parameter is set to [0] Do not reset, which is the default option.
Danfoss A/S © 2021.08
N O T I C E
Parameter Type: Option
Data Type: Uint8
N O T I C E
Name
Do not reset
Do reset
Parameter Type: Range, 0 - 20, Array [6]
Data Type: VisStr[20]
Parameter Type: Option
Data Type: Uint8
Parameter Descriptions
Setup: All set-ups
Change during operation: True
Description
Setup: 1 set-up
Change during operation: True
Setup: All set-ups
Change during operation: True
AU373327181955en-000101 / 130R1208 | 333