4.2.3 Busbars 4.2 Requirements This section describes the minimum recommended If the Danfoss busbar kit is not used, see Table 4.2 for the requirements for mechanical installation. For UL and CE cross-section measurements that are required when requirements, see chapter 5.2 Electrical Requirements for creating customized busbars.
Page 17
Each drive module contains a heat sink fan and a mixing fan. Typical enclosure designs utilize door fans along with the drive module fans to remove waste heat from the enclosure. Danfoss provides several back-channel cooling kits as options. These kits remove 85% of the waste heat from the enclosure, reducing the need for large door fans.
Remove the control shelf assembly from its package. Remove the LCP from the control shelf. Use some type of mounting bracket to install the control shelf. Danfoss does not supply the mounting brackets for the control shelf. For EMC-correct installation, refer to Illustration 4.7.
Electrical Installation Parallel Drive Modules NOTICE 5.7.2.2 KTY Sensor Danfoss is not responsible for the failure of any Klixon The frequency converter handles 3 types of KTY sensors: thermal switch. • KTY Sensor 1: 1 kΩ at 100 °C (212 °F). Philips KTY 84-1 is an example.
NOTICE 5.8.1.2 Mains Terminal Connections in 4- Drive Module Systems Danfoss is not responsible for any failure or malfunction in the disconnector/contactor switch. Illustration 8.11 shows the bus bar connections for 4-drive systems. If a common terminal design is used, there is 1 set of mains terminals in each cabinet.
Table 5.13 Discharge Resistors Recommended for Drive Systems with 525–690 V AC Mains Supply NOTICE Danfoss is not responsible for any failure or malfunction of the resistor, or for any misconnections made by the installer. NOTICE The wire used with the brake resistor should be double-insulated or have reinforced insulation.
Maximum 135% for s 1) Percentage relates to the nominal torque. Efficiency Efficiency 1) Efficiency measured at nominal current. For energy efficiency class, see . For part load losses, see www.danfoss.com/vltener- gyefficiency. 7.4 12-Pulse Transformer Specifications Connection Dy11 d0 or Dyn 11d0 Phase shift between secondaries 30°...
Installation Guide 8 Appendix 8.1 Disclaimer Conventions Numbered lists indicate procedures. Danfoss shall have no obligation with respect to any Bullet lists indicate other information and description of product that illustrations. • is not installed according to the standard configu- Italicized text indicates: ration as specified in the installation guide.
Page 84
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.