VLT® AutomationDrive EZ FC 321
Programming Guide
Parameter 14-32 Current Lim Ctrl, Filter Time
Table 493: Parameter 14-32 Current Lim Ctrl, Filter Time
14-32 Current Lim Ctrl, Filter Time
Default value: Size related
Conversion index: -4
Controls the current limit control low-pass filter. This makes it possible to react to peak values or to average values. When selecting
average values, it is sometimes possible to run with higher output current and instead trip on the hardware limit for current. Howev-
er, the control reacts slower as it does not react on immediate values.
Parameter 14-35 Stall Protection
Table 494: Parameter 14-35 Stall Protection
14-35 Stall Protection
Default Value: [1] Enabled
Conversion Index: -
This parameter is active in flux mode only.
Option
Name
Description
[0]
Disabled
Disables stall protection in field weakening flux mode and might cause the motor to be lost.
[1]*
Enabled
Enables stall protection in field weakening flux mode.
Parameter 14-36 Field-weakening Function
Table 495: Parameter 14-36 Field-weakening Function
14-36 Field-weakening Function
Default Value: [0] Auto
Conversion Index: -
Select the field-weakening function mode in flux mode.
Option
Option
Number
Name
[0]*
Auto
[1]
1/x
Parameter 14-37 Fieldweakening Speed
Table 496: Parameter 14-37 Fieldweakening Speed
14-37 Fieldweakening Speed
Default value: Size related
Conversion index: 67
Enter the start speed for option [1] [1/x] in parameter 14-36 Fieldweakening Function.
274 | Danfoss A/S © 2021.08
Parameter type: Range, 1 - 100 ms
Data type: Uint16
Parameter Type: Option
Data Type: Uint8
N O T I C E
Parameter Type: Option
Data Type: Uint8
Description
In this mode, the drive calculates the optimal torque output. Measured DC-link voltage determines
the phase-to-phase motor voltage. Magnetizing reference is based on the actual voltage and utilizes
the information about the model of the motor.
The drive reduces torque output. The drive sets the magnetizing reference inversely proportional to
the speed using a static curve that shows the relationship between DC-link voltage and the speed.
Parameter type: Range, 10 - 60000 RPM
Data type: Uint16
Parameter Descriptions
Setup: All setups
Change during operation: True
Setup: All set-ups
Change during operation: False
Setup: All set-ups
Change during operation: True
Setup: All setups
Change during operation: True