SPECIFICATIONS

CHAPTER3 SPECIFICATIONS

3.1 General Specifications

The following indicates the general specifications of the C Controller module.
Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Conforming
Vibration resistance
JIS B 3502,
IEC 61131-2
Shock resistance
Operating ambience
*5
Operating altitude
Installation location
Overvoltage
*1
category
*2
Pollution level
Table3.1 General specifications
Under
intermittent
to
vibration
Under
continuous
vibration
Conforming to JIS B 3502, IEC 61131-2 (147 m/s
* 1 This indicates the section of the power supply to which the equipment is assumed to be
connected between the public electrical power distribution network and the machinery within
premises. Category II applies to equipment for which electrical power is supplied from fixed
facilities.
The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
* 2 This index indicates the degree to which conductive material is generated in terms of the
environment in which the equipment is used.
Pollution level 2 is rated when only non-conductive pollution occurs. A temporary conductivity
caused by condensing can be expected occasionally.
* 3 The storage ambient temperature is -20 to 75
* 4 The operating ambient humidity and storage ambient humidity are 10 to 90%RH if the system
includes the AnS series modules.
* 5 Do not use or store the C Controller module under pressure higher than the atmospheric pressure
of altitude 0m.
Doing so can cause a malfunction.
For use in a pressurized environment, please contact your sales representative.
* 6 When installing a commercially available CompactFlash card into the C Controller module, please
follow the lower specifications of either the C Controller module or CompactFlash card.
*6
Specifications
0 to 55
*3
-25 to 75
*4
5 to 95%RH
, non-condensing
*4
5 to 95%RH
, non-condensing
Frequency
Acceleration
10 to 57Hz
----
2
57 to 150Hz
9.8m/s
10 to 57Hz
----
2
57 to 150Hz
4.9m/s
2
, 3 times in each of 3 directions X, Y, Z)
No corrosive gases
2000m (6562ft.) max.
Inside control panel
II max.
2 max.
if the system includes the AnS series modules.
3.1 General Specifications
Amplitude
Sweep count
0.075mm
(0.003inch)
10 times each
----
in X, Y, Z
0.035mm
directions
(0.001inch)
(for 80 min.)
----
3
- 1
1
2
3
4
5
6
7
8