FUNCTIONS

4.15 Interrupt from Intelligent Function Module

(1) Interrupt from intelligent function module
(2) Setting of interrupt from intelligent function module
4
- 102
4.15 Interrupt from Intelligent Function Module
The C Controller module can receive the interrupt event from the interrupt module and
the intelligent function module.
In the user program, create a program to receive an interrupt event and execute the
relevant processing using the QBF_WaitUnitEvent function.
To receive the interrupt from the intelligent function module, set "Intelligent function
module settings" by the <<System settings>> tab of the C Controller setting utility.
(a) Intelligent function module interrupt event settings
Figure 4.78 Intelligent function module interrupt event settings
1) CPU side "Interrupt event start No."
Set the interrupt event start No. on the C Controller module.
Setting range: 50 to 255
2) CPU side "Number of interrupt events"
Set the number of interrupt execution conditions set by the intelligent function
module.
Setting range: 1 to 16 (conditions)
3) Intelli. module side "Start I/O No."
Set the start I/O No. of the intelligent function module from which the interrupt
is to be performed.
Setting range: 0000 to 0FF0, 3E00 to 3E30(
4) Intelli. module side "Start SI No."
Set the intelligent function module interrupt pointer No. set at the intelligent
function module.
Setting range: 0 to 15
)