9
UTILITY OPERATION
9
- 29
9.2 C Controller Setting Utility
9.2.5 Operating Module monitoring screen
(d) Monitor and test
Module monitor and test (forced output of output (Y), forced write to buffer
memory and CPU shared memory) performed on this screen are executed for the
module installed to "Slot No." set on this screen.
They do not depend on the data in the "Type" field of Parameter settings (I/O
assignment settings).
Note that only the modules controlled by the C Controller module can be tested.
When monitoring or forcibly writing data to the buffer memory is performed to the
CC-Link module where data consistency verification per station function is set to
be enabled, the cyclic data are automatically refreshed.
Note that the data are automatically refreshed only when the monitoring or forcibly
writing data to the buffer memory is performed for the range of link refresh devices
(buffer memory), which correspond to the stations set in the CC-Link master
station parameters (Station information setting). (For details of the range, refer to
"Slave station offset, size information" (buffer memory address: 3E0
the buffer memory list for the CC-Link module.)
For details of the data consistency verification per station function, refer to the
following.
Section 4.3.1
Note also that the following areas are not refreshed when monitoring or forcibly
writing data to the buffer memory is performed.
• The write (transmission) area of link refresh devices (buffer memory) is not
refreshed when monitoring is performed.
• The read (reception) area of link refresh devices (buffer memory) is not
refreshed when the forced writing to the buffer memory is performed.
(e) Precautions for changing the module configuration
When the module configuration has been changed after a start of the C Controller
setting utility, performing any of the following operations updates the module
configuration information.
• Set the Connection settings.
• Click the
Start monitoring
• Click the
System info
button on the <<Module monitoring>> tab.
button on the <<Module monitoring>> tab.
to 5DF
) in
H
H