12
MULTIPLE CPU SYSTEM CONFIGURATION
Table12.11 Restrictions on system configuration, applicable base units, extension cables, power supply modules
CPU number
CPU module1: CPU No.1, CPU module 2: CPU No.2, CPU module 3: CPU No.3, CPU module 4: CPU No.4
Maximum number of
extension stages
Maximum number of
mounted I/O modules
Available main base
unit model
Type not requiring power supply module
Available extension
Type requiring Q series power supply
base unit model
module
Available extension
cable type
Available power
supply module model
7 extension stages (When using Q02UCPU: 4)
65 - (No. of CPUs configured) (When using Q02UCPU: 37 - (No. of CPUs configured))
QC05B, QC06B, QC12B, QC30B, QC50B, QC100B
Q61P-A1, Q61P-A2, Q61P, Q62P, Q63P, Q64P
* 1 When the Q02UCPU is mounted on CPU slot 1, CPU slot 4 is not available because the number of
mountable CPU modules is limited up to three.
Precautions
• Do not use extension cable longer than 13.2 m (43.28 feet).
• When using the extension cable, keep it away from the main circuit (high voltage,
large current).
• When setting the number of extension stages, prevent number duplication.
• If the Q5 B and Q6 B extension base units are used in the same system, there
are no restrictions on the connection order for them.
Refer to the QCPU User's Manual (Hardware Design, Maintenance and
Inspection) and check if they can be used.
• The QA1S6 B and Q6 RB cannot be used as an extension base unit.
• Connect the extension cable from OUT of the extension cable connector of the
base unit to IN of the next extension base unit.
• When 66 or more modules (37 or more when using the Q02UCPU) are mounted,
an intelligent function module assignment error (error code: 2124, SP. UNIT LAY
ERR.) occurs. (Including CPU modules)
• "Number of CPUs configured" indicates the number of CPU modules set in
"Number of CPUs" on the <<Multiple CPU settings>> tab of the C Controller
setting utility.
• Refer to the manuals of the corresponding CPU modules for details of
programmable controller CPUs and Motion CPUs.
• Only when CPU No.1 is the Q02UCPU, a Motion CPU (except for Q172DCPU
and Q173DCPU) can be mounted.
• The Q172DCPU and Q173DCPU cannot be mounted.
12.1.7 System configuration (When CPU No.1 is Universal model QCPU)
Q33B, Q35B, Q38B, Q312B
Q52B, Q55B
Q63B, Q65B, Q68B, Q612B
12.1 System Configuration
9
*1
10
11
12
13
14
15
16
12
- 25