Resetting Cpu Module - Mitsubishi MELSEC-Q Series User Manual

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

13
MULTIPLE CPU SYSTEM CONCEPT

13.6 Resetting CPU Module

The entire multiple CPU system can be reset by resetting CPU No.1.
The CPU modules of No.2 to No.4, I/O modules and intelligent function modules will be
reset when CPU No.1 is reset.
If a stop error has occurred in any of the CPUs on the multiple CPU system, either reset
CPU No.1 or restart the multiple CPU system (power supply ON
recovery.
The system will not be recovered by resetting the error-stopped CPU module other than
CPU No.1.
(Example) In the case of C Controller module
CPU
0
1
1
2
3
The overall multiple CPU system can be reset.
Figure 13.26 Resetting of multiple CPU system
POINT
1. It is not possible to reset the CPU modules of No.2 to No.4 individually in the
multiple CPU system.
If any CPU module other than CPU No. 1 is reset during operation of the
multiple CPU system, a multi CPU error (error code: 7000, MULTI CPU
DOWN) occurs in the other CPUs and the entire multiple CPU system stops.
Note that, depending on the reset timing of any CPU module other than CPU
No. 1, an error other than the multi CPU error (error code: 7000, MULTI CPU
DOWN) may stop the other CPU modules.
2. If any CPU module other than CPU No. 1 is reset, a multi CPU error (error
code: 7000, MULTI CPU DOWN) occurs regardless of the Operation mode
setting (All CPUs stopped due to an error in CPU n/Continue) on the
<<Multiple CPU settings>> tab of the C Controller setting utility. (
13.7)
Slot number
Slot number
2
3
4
5
6
7
Control CPU setting
1 1
1 1
1
2
3 3
3 3 3 3
4
4
4
Resetting is not allowed in the multiple CPU system,
Doing so will result in "MULTI CPU DOWN" in all CPUs
in the multiple CPU system.
13.6 Resetting CPU Module
OFF
ON) for
Section
13
- 29
9
10
11
12
13
14
15
16

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q06ccpu-vMelsec q06ccpu-v-bMelsec sw3pvc-ccpu-e

Table of Contents