9
UTILITY OPERATION
Table9.62 Explanation of Detailed module information screen (Continued)
Item
Control station information
Assign control station
Present control station
Transmission information
Sub control station
transmission
Remote I/O master station
number
Block 1
Block 2
Link information
Mode
F loop status
Loopback station
R loop status
Loopback station
Link scan time
Max.
Min.
Current
Description
Displays the control station information of the MELSECNET/H
network system.
Displays the specified control station in the MELSECNET/H
network system.
"0" appears when the control station is faulty.
Displays the present control station in the MELSECNET/H
network system.
"0" appears when the control station is faulty.
Displays the transmission information of the MELSECNET/H
network system.
(Display item: "Control station communication", "Sub control
station transmission")
Displays the sub control station transmission status of the
MELSECNET/H network system.
(Display item: "Yes", "No")
Displays the station No. of the remote I/O master station in each
block.
Displays the station No. of the remote I/O master station in Block
1.
Displays the station No. of the remote I/O master station in Block
2.
Displays the network status.
Displays the operating mode of the own station.
(Display item: "Online", "Offline", "Loop test")
Displays the forward loop status.
(Display item: "Normal", "Loopback transmission", "Data link
*2
disable", "-"
)
Displays the number of the station that is performing loopback
on the forward loop side.
(Display range: 1 to 64, "Not performed", "(blank)"
Displays the reverse loop status.
(Display range: "Normal", "Loopback transmission", "Data link
*2
disable", "-"
)
Displays the number of the station that is performing loopback
on the reverse loop side.
(Display range: 1 to 64, "Not performed", "(blank)"
Displays the link scan time. (Unit: ms)
Displays the maximum link scan time in the past.
"(Blank)" appears when data link is not available.
Displays the minimum link scan time in the past.
"(Blank)" appears when data link is not available.
Displays the current link scan time.
"(Blank)" appears when data link is not available.
* 2 The symbol, "-" appears in the case of a coaxial bus system.
* 3 "(Blank)" appears when data link is not available.
*3
*2
, "-"
*3
*2
, "-"
9.4 MELSECNET/H Utility
9.4.2 Operating Module information screen
Correspon-
Correspon-
ding SB
ding SW
SW0057
SW0056
SB0056
SB0058
SW005C
SW005D
SW0043
SB0091,
SB0099
SW0099
)
SB0095,
SB009A
SW009A
)
SW006B
SW006C
SW006D
(To next page)
9
- 96