Setting And Wiring Hardware; Mounting And Setting The Master Unit - Omron DeviceNet CV Series Operation Manual

Devicenet slaves
Table of Contents

Advertisement

Setting and Wiring Hardware

2-3
Setting and Wiring Hardware
2-3-1

Mounting and Setting the Master Unit

Settings
Front panel
16
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
supplied. In the examples shown here, the power is supplied from one com-
munications power supply, and communications cables are connected using
T-branch Taps.
Refer to the DeviceNet Operation Manual (W267) for details on methods of
supplying communications power.
Note Use the OMRON Connectors shown below when using Thick Cables and
multi-drop connections for wiring.
XW4B-05C4-T-D
(Without set screws)
Use the following procedures to mount, set, and wire the hardware.
The components, functions, and switch settings for the C200HW-DRM21-V1
Master Unit mounted to a C200HX PLC are shown as an example in the fol-
lowing diagram. For information on switch settings and other Master Units,
refer to the operation manual for the Master Unit.
Rear-panel DIP switch
Indicators
These pins have the following
functions:
Pins 1 to 6: Node address
Pins 7 and 8: Reserved (Always OFF.)
Here, all pins are set to OFF to set the
node address to 01
Rotary switch
This switch sets the Master's single-digit hexadecimal
unit number. Here, set this switch to 0.
Front-panel DIP switch
These pins have the following functions:
Pins 1 and 2: Baud rate
Pin 3: Continue/stop communications for error
Pin 4: Reserved (Always OFF.)
Here, all pins are turned OFF to set the baud rate to
125 Kbps and to continue communications for errors.
Communications connector
Section 2-3
XW4B-05C4-TF-D
(With set screws)
Rear panel